Quick Reference Guide

CMC version 3.00 accepts IPv4, IPv6, or fully qualified domain names (FQDN) for both
FTP and TFTP servers.
NOTE: You can specify the cmc-active and cmc-standby modules at the same time
along with one or more server-n modules. This enables the devices to be updated
together. This option is applicable only for CMC.
When you use the server-generation option, the CMC updates all iDRACs of that
particular generation that can be updated.
NOTE: Verify that the update applied to servers for a particular generation has been
validated for all impacted server models.
Output Displays a message indicating the operation that is being performed.
Example
Upload the firmware image from the TFTP server and start the firmware update
racadm fwupdate -g -u -a 192.168.0.100 -d
firmimg.cmc -m cmc-active TFTP firmwareate has been
initiated. This update process may take several
minutes to complete.
.
Upload the firmware image from the FTP server and start the firmware update.
racadm fwupdate -f 192.168.0.100 fred password123 -d
firmimg.cmc -m cmc-active
Start IOM infrastructure firmware update.
racadm fwupdate -u -m iominf-1
Update firmware on both the CMCs.
racadm fwupdate -g -u -a 192.168.0.100 -d
firmimg.cmc -m cmc-active -m cmc-standby
Update firmware on multiple servers.
racadm fwupdate -g -u -a 192.168.0.100 -d
firmimg.imc -m server-1 -m server-2 -m server-3
Update firmware on servers of iDRAC generation.
racadm fwupdate -g -u -a 192.168.0.100 -d
firmimg.imc -m server-iDRAC
Update firmware on multiple IOM infrastructure devices.
racadm fwupdate -u -m iominf-4 -m iominf-5 -m
iominf-6
Query the current status of all firmware targets to be updated.
racadm fwupdate -s -m all
Download firmware update file from a specified location on the TFTP server at
a specific IP address.
racadm fwupdate -g -u -a 143.166.154.143 -d <path>
After the image file is downloaded from the TFTP server, the update process
begins. When completed, iDRAC is reset.
Read the current status of the firmware update.
racadm fwupdate -s
NOTE: Firmware update from local racadm (using -p -u -d options) is not supported
on linux OS.
NOTE: For CMC, these commands specifically apply to an active-CMC update.
The following table describes the firmware update method supported for each interface.
39