CLI Guide
where 0 is disable and 1 is enable.
Input • -i <slot#> <state> — Enables or disables FlexAddress for the specified slot.
• -f <fabricName> <state> — Enables or disables FlexAddress for the specified fabric.
Example
• racadm setflexaddr -i 1 0
Slot 1 FlexAddress state set successfully
•
racadm setflexaddr -f A 1
Fabric A FlexAddress state set successfully
•
racadm setflexaddr -f idrac 1
setled
Table 121. Details of setled
Description Sets the state (blinking or not blinking) of the LED on the specified module.
To blink or unblink the chassis, I/O modules or the CMC, you must have the Debug Administrator privilege on
CMC. To enable the servers to blink or unblink, you must have the Server Administrator or Debug
Administrator privilege on CMC.
Synopsis
racadm setled -m <module> -l <ledState>
Input • -m <module> - Specifies the module whose LED you want to configure.
<module> can be one of the following:
— server-n, where n=1–4
— switch-n, where n=1
— cmc-active
— chassis
• -l <ledstate> - Specifies whether the LED should blink.
<ledstate> can be one of the following:
– 0 — no blinking
– 1 — blinking
Example
• racadm setled -m server-1 -1 1
LED state was set successfully.
NOTE: The setled command generates an error when used on the extension slot of a multi-slot
server.
• racadm setled -m server-9 -1 1
ERROR: Server in slot 9 is an extension of the server in slot 1.
set enclosure
Table 122. Details of set enclosure
Description Sets the asset tag and asset name of the enclosures.
RACADM Subcommand Details 99