You cannot specify which index is used. If the index already exists, it is either used or the new entry is created in the rst available index
for that group.
The racadm getconfig -f <filename>.cfg command places a comment in front of index objects, allowing you to see the
included comments.
NOTE: You may create an indexed group manually using the following command:
racadm config -g <groupname> -o <anchored object> -i <index 1-4> <unique anchor name>
The line for an indexed group cannot be deleted from a .cfg le. If you do delete the line with a text editor, RACADM stops when it
parses the conguration le and alert you of the error.
You must remove an indexed object manually using the following command:
racadm config -g <groupname> -o <objectname> -i <index 1-4> ""
NOTE: A NULL string (identied by two " characters) directs the CMC to delete the index for the specied
group.
To view the contents of an indexed group, run the following command:
racadm getconfig -g <groupname> -i <index 1-4>
For indexed groups the object anchor must be the rst object after the [ ] pair. The following are examples of the current indexed
groups:
[cfgUserAdmin]
cfgUserAdminUserName= <USER_NAME>
When using remote RACADM to capture the conguration groups into a le, if a key property within a group is not set, the
conguration group is not saved as part of the conguration le. If these conguration groups are needed to be cloned onto other
CMCs, the key property must be set before executing the getconfig -f command. Alternatively, you can manually enter the
missing properties into the conguration le after running the
getconfig -fcommand. This is true for all the RACADM–indexed
groups.
This is the list of the indexed groups that exhibit this behavior and their corresponding key properties:
cfgUserAdmin — cfgUserAdminUserName
cfgEmailAlert — cfgEmailAlertAddress
cfgTraps — cfgTrapsAlertDestIPAddr
cfgStandardSchema — cfgSSADRoleGroupName
cfgServerInfo — cfgServerBmcMacAddress
Modifying the CMC IP Address
When you modify the CMC IP address in the conguration le, remove all unnecessary <variable> = <value> entries. Only the
actual variable group’s label with [ and ] remains, including the two <variable> = <value> entries pertaining to the IP address
change.
Example:
#
# Object Group "cfgLanNetworking"
#
[cfgLanNetworking]
cfgNicIpAddress=10.35.10.110
cfgNicGateway=10.35.10.1
This le is updated as follows:
#
# Object Group "cfgLanNetworking"
#
[cfgLanNetworking]
cfgNicIpAddress=10.35.9.143
Conguring