Quick Reference Guide

RACADM Subcommands 97
Usage
racadm setniccfg [-m <module>] [-d] [-o] [-6] [-s
<ipaddress> <subnetmask> <gateway>] [-k <speed>
<duplex>]
racadm setniccfg [-m <module>] -d
racadm setniccfg [-m <module>] -s <ipAddress>
<netmask> <gateway>
racadm setniccfg [-m <module>] -v [<vlan id> <vlan
priority>]
racadm setniccfg [-m <module>] -o
racadm setniccfg [-m <module>] -p [-6]
racadm setniccfg [-m <module>] -k [<speed> <duplex>]
Options
Table 2-38. setniccfg Subcommand Options
Option Description
-m <module> Specifies the module for which you want to set the IP
configuration.
<module> can be any of the following:
server-n
where
n=
1–16
switch-n
where
n=
1–6
chassis
If the -m option is excluded, the module defaults to
chassis.
-d
Enables DHCP for the Ethernet management port (default is
DHCP enabled).
-6
Displays the IPv6 information.
-s
Enables static IP settings by specifying the IP address, subnet
mask, and gateway. <ipAddress>, <netmask>, and
<gateway> must be typed as dot-separated strings.
If this option is not supplied, the existing static settings are
used.