cfgEmailAlert cfgEmailAlertAddress
cfgTraps cfgTrapsAlertDestIPAddr
cfgStandardSchema cfgSSADRoleGroupName
cfgServerInfo cfgServerBmcMacAddress
Modifying the CMC IP Address
When you modify the CMC IP address in the configuration file, remove all unnecessary <variable> = <value> entries. Only
the actual variable groups label with [ and ] remains, including the two <variable> = <value> entries pertaining to the IP
address change.
Example:
#
# Object Group "cfgLanNetworking"
#
[cfgLanNetworking]
cfgNicIpAddress=10.35.10.110
cfgNicGateway=10.35.10.1
This file is updated as follows:
#
# Object Group "cfgLanNetworking"
#
[cfgLanNetworking]
cfgNicIpAddress=10.35.9.143
# comment, the rest of this line is ignored
cfgNicGateway=10.35.9.1
The command racadm config -f <myfile>.cfg parses the file and identifies any errors by line number. A correct file
updates the proper entries. Additionally, you can use the same getconfig command from the previous example to confirm the
update.
Use this file to download company-wide changes or to configure new systems over the network with the command, racadm
getconfig -f <myfile>.cfg.
NOTE: Anchor is a reserved word and should not be used in the .cfg file.
Configuring Multiple CMCs through RACADM Using
Chassis Configuration Profiles
By using chassis configuration profiles, you can export the chassis configuration profiles as an XML file and import it to another
chassis.
Use RACADM get command for export operation and set command for import operation.You can export chassis profiles (XML
files) from CMC to the network share or to a local management station and import chassis profiles (XML files) from the network
share or from a local management station.
NOTE: By default, the export is done as clone type. You can use the clone to get the clone type profile in XML file.
The import and export operation to and from the network share can be done through local RACADM as well as remote
RACADM. Whereas, the import and export operation to and from the local management can be done only through remote
RACADM interface.
Exporting Chassis Configuration profiles
You can export chassis configuration profiles to network share by using the get command.
Configuring CMC