Users Guide

Configuring Sled Power Button
You can configure the Sled Power Button to disable, so that when you press the Sled power button, it has no effect. To configure the
Sled Power Button, go to Chassis Overview > Server Overview > Power > Control.
Under the Property section, select the check box to disable or clear the check box to enable.
NOTE: This setting is applicable only to multi-node Sleds present in the chassis. Other Sleds are not affected.
AC Power Recovery
If the AC power supply of a system is disrupted, the chassis is restored to the previous power state before the AC power loss. The
restoration to the previous power state is the default behavior. The following factors could cause the disruption:
power outage
power cables pulled from the power supply units (PSUs)
power distribution unit (PDU) outage
If the Budget/Redundancy Configuration > Disable AC Power Recovery option is selected, the chassis remains powered off after
the AC recovery.
In case, the blade servers are not configured to automatic power-up, you may have to power them on manually.
Managing and monitoring power 141