CLI Guide

Table 89. Details of set (continued)
Configure a CMC from an XML configuration file on a remote NFS share
racadm set -f myfile.xml -t xml -l 192.168.0.0:/myshare
setassettag
Table 90. Details of setassettag
Description Sets the N-byte ASCII asset tag for the chassis.
To use this subcommand, you must have the Administrator privilege.
NOTE: The special characters " (double quote), ` (back quote), & (ampersand), and \
(backslash) are not supported for this subcommand.
Synopsis
racadm setassettag -m chassis <asset tag>
Input -m < module > — Specifies the module whose asset tag you want to set.
Legal value: chassis
You can obtain the same output if you do not include this option, because there is only one legal
value.
< assettag > is a maximum of 64 non-extended ASCII characters.
Example
racadm setassettag -m chassis 783839–33
racadm setassettag 783839–33
The asset tag was changed successfully.
setchassisname
Table 91. Details of setchassisname
Description Sets the name of the chassis.
To use this subcommand, you must have the Administrator privilege.
NOTE: The special characters " (double quote), ` (back quote), & (ampersand), >
(greater than), < (less than), and \ (backslash) are not supported for this
subcommand.
Synopsis
racadm setchassisname <name>
NOTE: Chassis name is a maximum of 64 unextended ASCII characters.
Example
racadm setchassisname dellchassis-1
The chassis name was set successfully.
82 RACADM Subcommand Details