CLI Guide

cfgChassisPowerCapFPercent (Read/Write)
Table 279. Details of cfgChassisPowerCapFPercent
Description Indicates the power consumption limit as a percentage. The percentage is computed mathematically as
the minimum power + (percent * (maximum power - minimum power)). Use
cfgChassisPowerCapFPercent when power consumption is to be changed regardless of whether
server throttling is required.
Legal Values 16 - 100
NOTE: If the specied percent is lower than the minimum value, the CMC will set the value
to the minimum value.
Default 100
cfgChassisRedundancyPolicy (Read/Write)
Table 280. Details of cfgChassisRedundancyPolicy
Description Sets the redundancy policy of the chassis.
Legal Values
0 — No redundancy
1 — Grid redundancy
3 — Redundancy alerting only
4 — Fault tolerant redundancy
Default 3 — Redundancy alerting only
cfgChassisInMaxPowerCapacity (Read Only)
Table 281. Details of cfgChassisInMaxPowerCapacity
Description Indicates the total chassis power budget (in watts) available for chassis operation.
Legal Values None
Default None
148 CMC Property Database Group and Object Descriptions