CLI Guide
cfgChassisRedundancyPolicy (Read/Write)
Description Sets the redundancy policy of the chassis.
Legal Values
• 0 — No redundancy
• 1 — Grid redundancy
• 3 — Redundancy alerting only
• 4 — Fault tolerant redundancy
Default 3 — Redundancy alerting only
cfgChassisInMaxPowerCapacity (Read Only)
Description Indicates the total chassis power budget (in watts) available for chassis operation.
Legal Values None
Default None
cfgChassisInRedundancyReserve (Read Only)
Description
Indicates the amount of redundant power (in Watts) in reserve that can be utilized in the event of an
AC grid or PSU failure. This value is 0 if the Redundancy Policy is set to 0 (no redundancy).
Legal Values 0 (disabled)
1 (enabled)
Default None
cfgChassisPowerClear (Write Only)
Description
Resets cfgChassisMinPower and cfgChassisMaxPowerCapacity, when set to 1.
Legal Values None
Default None
cfgChassisPowerClearTimestamp (Read Only)
Description
Time stamp when cfgChassisMinPower and cfgChassisMaxPowerCapacity were reset.
Legal Values None
CMC Property Database Group and Object Descriptions 133