Reference Guide

— powerdown — Turns o the managed system.
— powerup — Turns on the managed system.
— powerstatus — Displays the current power status of the server (ON or OFF).
— reseat — Performs a virtual reseat of the server. This operation simulates reseating the
server by resettig the iDRAC on a server.
NOTE: The reseat option is not available for individual FM120 servers.
NOTE: The action powerstatus is not allowed with an -a option.
Output Displays an error message if the requested operation fails, or a success message if the operation
is completed.
Example
Turn o server 3 from the CMC
racadm serveraction -m server-3 powerdown
Server power operation successful
Turn o server 3 from iDRAC
racadm serveraction powerdown
Server power operation successful
Turn o server 3 from CMC when Power is already turned o on that server
racadm serveraction -m server-3 powerdown
Server is already powered OFF.
Turn o the server from CMC when Power is already turned o on that server.
racadm serveraction powerdown
Server is already powered OFF
Get Power Status of server 2 on CMC
racadm serveraction -m server-2 powerstatus
ON
Get Power status action on multinode server:
racadm serveraction -m server-1a powerstatus
Get Power Status on iDRAC
racadm serveraction powerstatus
Server Power Status: ON
Reseat action on a multinode sled
racadm serveraction -f -m sled-1 reseat
Explanation of Support
CMC needs to support graceful shutdown
The support of address individual blades is expected on the CMC
set
Description
Import saved CMC conguration or CMC Event Filter conguration from a le.