Reference Guide

Input
NOTE: Firmware update from local RACADM (using the -p, -u, or -d options) is not
supported on Linux operating system.
-p — The -p option is used to update the rmware le from the client. The -u option must
be used with the -p option.
-f — The FTP is used to download the rmware.
-g — For CMC, the rmware is downloaded using the TFTP server.
-u — The rmware update operation is performed.
-a Species the TFTP server IP address or FQDN used for the rmware image (used
with -g).
NOTE: CMC accepts IPv4, IPv6, or fully qualied domain names (FQDN) for both
FTP and TFTP servers.
-d Species the source path where the rmware image is stored.
NOTE: The default source path is local Default: Designated TFTP default directory
on that host for the le if -g option is absent. If -g is used, it defaults to a directory
congured on the TFTP server.
-o — Turns o the servers to perform an update.
-m < module >—
Species the module or device to be updated. < module > is one of the following values:
NOTE: You can also specify multiple modules:
–m <module 1> –m <module 2>
, and
so on.
cmc
iominf-n, where n = 1
main-board
hdd-fqdd, where fqdd is FQDD of the HDD
-s — Displays the current status of the rmware update.
NOTE: Use -m to display the status of the module update. Omit -m to display the
status of the CMC update.
NOTE: Use all to get the status of all the targets that must be updated.
-c — Cancels the current rmware update of a module.
Output
Displays a message indicating the operation that is being performed.
Example
NOTE: The following commands apply to CMC update.
Upload a rmware image from the client and start rmware update:
racadm fwupdate -p -u -d fx2_cmc.bin
Upload the rmware image from the TFTP server and start the rmware update:
racadm fwupdate -g -u -a 192.168.0.100 -d fx2_cmc.bin -m cmc-
active
TFTP firmwareate has been initiated. This update process may
take several minutes to complete.
Upload the rmware image from the FTP server and start the rmware update.
racadm fwupdate -f 192.168.0.100 root <default root password> -
d fx2_cmc.bin -m
Start IOM infrastructure rmware update.
racadm fwupdate -u -m iominf-1
View the current rmware update status:
racadm fwupdate –s –m
29