cfgChassisPowerCapPercent (Read/Write)
Description Indicates the power consumption limit as a percentage. The percentage is computed
mathematically as the minimum power + (percent * (maximum power - minimum power)). The
command generates an error if server throttling is necessary to achieve the power goal based on
the value for this setting.
Legal Values 16 - 100
NOTE: If the specied percent is lower than the minimum value, the CMC will set the
value to the minimum value.
Default 100
cfgChassisPowerCapFPercent (Read/Write)
Description Indicates the power consumption limit as a percentage. The percentage is computed
mathematically as the minimum power + (percent * (maximum power - minimum power)). Use
cfgChassisPowerCapFPercent when power consumption is to be changed regardless of
whether server throttling is required.
Legal Values 16 - 100
NOTE: If the specied percent is lower than the minimum value, the CMC will set the
value to the minimum value.
Default 100
cfgChassisRedundancyPolicy (Read/Write)
Description
Sets the redundancy policy of the chassis.
Legal Values
• 0 (no redundancy)
• 1 (Grid redundancy)
• 3 ( Redundancy Alerting Only)
Default 3 ( Redundancy Alerting Only)
cfgChassisInMaxPowerCapacity (Read Only)
Description
Indicates the total chassis power budget (in watts) available for chassis operation.
Legal Values None
Default None
cfgChassisInRedundancyReserve (Read Only)
Description
Indicates the amount of redundant power (in Watts) in reserve that can be utilized in the event of
an AC grid or PSU failure. This value is 0 if the Redundancy Policy is set to 0 (no redundancy).
Legal Values 0 (disabled)