Owner's Manual

194 Power Management
For example, the following command:
racadm config -g cfgChassisPower -o
cfgChassisDynamicPSUEngagement 0
disables dynamic power supply engagement.
To select a redundancy policy, type:
racadm config -g cfgChassisPower -o
cfgChassisRedundancyPolicy <
value
>
where
<
value
>
is
0
(No Redundancy), 1 (AC Redundancy),
2
(Power Supply Redundant). The default is 0.
For example, the following command:
racadm config -g cfgChassisPower -o
cfgChassisRedundancyPolicy 1
sets the redundancy policy to 1.
To enable or disable dynamic PSU engagement, type:
racadm config -g cfgChassisPower -o
cfgChassisDynamicPSUEngagement <
value
>
where
<
value
>
is
0
(disable), 1 (enable). The default is 1.
For example, the following command:
racadm config -g cfgChassisPower -o
cfgChassisDynamicPSUEngagement 0
disables dynamic PSU engagement.
For information about RACADM commands for chassis power:
See "config" on page 268
See "getconfig" on page 274
See "getpbinfo" on page 286
See "cfgChassisPower" on page 350