Owner's Manual
Power Management 191
Configuring Power Budget and Redundancy
The CMC’s power management service optimizes power consumption for the
entire chassis (the chassis, servers, IOMs, iKVM, CMC, and PSUs) and re-
allocates power to different modules based on the demand.
Using the Web Interface
NOTE: To perform power management actions, you must have Chassis Control
Administrator privilege.
1
Log in to the CMC Web interface.
2
Select
Chassis
in the system tree.
3
Click the
Power Management
tab. The
Power Budget Status
page
displays.
4
Click the
Configuration
sub-tab. The
Budget/Redundancy Configuration
page displays.
5
Set any or all of the properties described in Table 7-12 according to your
needs.
6
Click
Apply
to save your changes.
To refresh the content on the Budget/Redundancy Configuration page, click
Refresh. To print the contents, click Print.
Table 7-12. Configurable Power Budget/Redundancy Properties
Item Description
System Max AC
Power Limit
Indicates the user-defined maximum power consumption limit
for the entire system (chassis, CMC, servers, I/O modules,
power supply units, iKVM, and fans). The CMC will enforce
this limit when power conservation mode is enabled (by
checking Server Power Throttling Enabled), or by powering off
lower priority blades if power conservation mode is not enabled.
The power budget is limited to a maximum of three PSUs out
of a total of six PSUs. If you attempt to set an AC power
budget value that exceeds the power capacity of your chassis,
the CMC will display a failure message.
Configuration range: 2768–7928 watts
Default: 7928 watts