VLT0103
Message Processor module
arg1
voltage is greater than the upper critical threshold.
Arguments
•
arg1 =
name
Detailed
Description
System hardware detected an over voltage or under voltage condition. If multiple voltage
exceptions occur consecutively the system may power down in failsafe mode.
Recommended
Response Action
1) Review system logs for power supply exceptions. 2) Remove the processor module. Inspect
processor socket for bent pins. 3) If the problem persists, contact technical support. Refer to
the product documentation to choose a convenient contact method.
Category System Health
SubCategory VLT = Voltage
Severity Severity 1 (Critical)
Trap/EventID FALSE
LCD Message Processor module <name> voltage is outside of range . Contact support
Initial Default. FALSE
Filter
Visibility
IPMI Alert SNMP
Alert
Email
Alert
LC Log LCD Power Off Power
Cycle
Reset
FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE FALSE
VLT0104
Message Processor module
arg1
voltage is outside of range.
Arguments
•
arg1 =
name
Detailed
Description
System hardware detected an over voltage or under voltage condition. If multiple voltage
exceptions occur consecutively the system may power down in failsafe mode.
Recommended
Response Action
1) Review system logs for power supply exceptions. 2) Remove the processor module. Inspect
processor socket for bent pins. 3) If the problem persists, contact technical support. Refer to
the product documentation to choose a convenient contact method.
Category System Health
SubCategory VLT = Voltage
Severity Severity 1 (Critical)
Trap/EventID FALSE