Reference Guide

PSU0004
Message The power input for power supply
arg1
is outside of range.
Arguments
arg1 =
number
Detailed
Description
The operating requirements for the power supply may be found in product documentation or on
the power supply itself.
Recommended
Response Action
Verify the input source is attached to the power supply. Verify the input power is within the
operating requirements for the power supply.
Category System Health
SubCategory PSU = Power Supply
Severity Severity 1 (Critical)
Trap/EventID 2185
LCD Message Power input for PSU <number> is outside of range. Check PSU cables
Initial Default. LC Log
Filter
Visibility
IPMI Alert SNMP
Alert
Email
Alert
LC Log LCD Power Off Power
Cycle
Reset
TRUE FALSE TRUE TRUE TRUE FALSE FALSE FALSE FALSE
PSU0005
Message The power input for power supply
arg1
is outside of the allowable range, but it is attached to the
system.
Arguments
arg1 =
number
Detailed
Description
The operating requirements for the power supply may be found in product documentation or on
the power supply itself.
Recommended
Response Action
Verify the input power is within the operating requirements for the power supply.
Category System Health
SubCategory PSU = Power Supply
Severity Severity 2 (Warning)
Trap/EventID 2186
LCD Message No LCD message display defined.
Initial Default. LC Log
525