Reference Guide

Trap/EventID FALSE
LCD Message No LCD message display defined.
Initial Default. LC Log
Filter
Visibility
IPMI Alert SNMP
Alert
Email
Alert
LC Log LCD Power Off Power
Cycle
Reset
FALSE FALSE FALSE FALSE TRUE FALSE FALSE FALSE FALSE
PSU8505
Message Unable to set the chassis redundancy policy to AC Redundancy.
Detailed
Description
Unable to set the chassis redundancy policy to AC Redundancy.
Recommended
Response Action
Retry the operation using the CMC command line interface or CMC Web interface. To set the
chassis redundnacy policy using the command line, enter "racadm config -g cfgChassisPower -
o cfgChassisRedundancyPolicy 1". To configure the chassis redundancy policy using the Web
interface, click Chassis Overview > Power > Configuration. From the Redundancy drop-down
menu, select AC Redundancy.
Category Audit
SubCategory PSU = Power Supply
Severity Severity 1 (Critical)
Trap/EventID FALSE
LCD Message No LCD message display defined.
Initial Default. LC Log
Filter
Visibility
IPMI Alert SNMP
Alert
Email
Alert
LC Log LCD Power Off Power
Cycle
Reset
FALSE FALSE FALSE FALSE TRUE FALSE FALSE FALSE FALSE
PSU8506
Message Unable to change power cap because Server Based Power Management Mode is enabled.
Detailed
Description
When the Server Power Management mode is enabled the Power cap cannot be set.
Recommended
Response Action
To enable the ability to set the power cap, switch to external Power Management and disable
the Server Based Management Mode in the CMC Web interface.
Category Audit
SubCategory PSU = Power Supply
Severity Severity 2 (Warning)
Trap/EventID FALSE
511