Rack Mounting
When you prepare your equipment rack:
• Make sure that the rack is bolted to the floor and braced to a wall or ceiling.
• Make sure that the rack is permanently grounded to earth ground. The equipment rack must be grounded
to the same ground point used by the service in your area.
• The AC cord is the primary ground.
When you install the chassis, use a level to ensure the chassis is installed level.
Requirements
There are two types of power supplies: Power Supply 1200W-AC and Power Supply 1600W-AC. The
minimum and the redundant power supplies required to operate is listed in the table below. Dell
Networking recommends the redundancy configuration.
The C300 requirements are given below:
Voltage Minimum PSUs
Minimum with
Redundant PSUs
Power Supply 1200W-AC/Power Supply
1600W-AC
100-120 2 3
Power Supply 1200W-AC 200-240 2 3
Power Supply 1600W-AC 200-240 1 2
Table 3-1. System Specifications
Parameter Specifications
Nominal Input Voltage 100 - 240 VAC 50/60 Hz
Maximum AC Power Supply Input Current
(Based on 1200 W output for 100/120 V and
1600 W 200/240 V lines)
14 A @ 100 V per AC Power Supply
11 A @ 120 VAC per AC Power Supply
9 A @ 200 VAC per AC Power Supply
7 A @ 240 VAC per AC Power Supply
Maximum System Power Input 9,667 KVA @ 100/120 V
12,596 KVA @ 200/240 V
Maximum Thermal Output at 100/120V 9,235 BTU/hour
Maximum Thermal Output at 200/240V 9,299 BTU/hour