Datasheet

INPUT
Voltage (AC)
100 V to 240 V
Frequency
50 Hz to 60 Hz
Current
0.4 A @ AC 90 V input
Inrush Current
40 A @ AC 240 V input
Leakage Current
< 0.1 mA @ AC 240 V input
PROTECTION
Over Current
Yes
Short Circuit
Output protected, auto recovery after short circuit condition has been removed
OTHERS
Standby Power
0.3 W max.
Cooling
Free air convection
Withstand Voltage
I/P-O/P: AC 4177 V or DC 5931 V / 1 minute
Insulation Resist.
I/P-O/P, I/P-FG: DC 500 V / 10,000 Ohm
Environment
Temperature
Operating: 0 °C to 40 °C / Storage: -20 °C to 60 °C
Humidity
5 % RH to 95 % RH
Connection
Input
Interchangeable Plugs (Standard): CEE 7/16 (Europlug) / BS 1363 (UK) / NEMA (US)
Optionally available upon request: AS/NZS 3112 (AU) / CPCS-CCC (CN)
Output
Standard Plug: 2.1 mm x 5.5 mm x 9.5 mm, center positive or customers’ requirements // Cable: 180 cm
M.T.B.F.
50,000 hours (according to MIL-HDBK-217F in 25 °C environment)
SAFETY APPROVED
IEC 60950-1:2006 2
nd
ed. / IEC 60601-1:2005 / EN 60950-1:2006 / EN 60601-1:2006 / UL 60950-1
UL 60601-1 / EN 61347-1:2008 / EN 61347-2-13:2006 / PPP 76001:2008 incl. 01 2-08
PSE-JET / C-Tick (AS / NZS 3200 Medical) / CCC (ITE GB4943)
EMC
EN 60601-1-2:2007 / EN 61000-3-2:2006 / EN 61000-3-3:1995+A2:2005
WEIGHT
N.W.: 120 g without interchangeable AC plug