Datasheet

Specifications subject to change without notice
ATM 200T IT / Medical 200 W
Product similar to photo, variations possible.
Features
Suitable for IT and Medical Equipment
IEC/EN/ANSI/AAMI ES60601-1 (Edition 3.1)
EMC: IEC 60601-1-1-2 (Edition 4.0)
Means of Protection: 2x MOPP
Touch Current: < 100 µA
Universal Input 100 V 240 V AC
Compliant to DoE 2016 (Level VI)
Regulated Output with Low Ripple Noise
1 Year Warranty
Marks / Approvals
Specifications
MODEL
Voltage
Max. Load
Max. Power
ATM 200T-120
12 V
16.00 A
192 W
ATM 200T-A150
15 V
13.00 A
195 W
ATM 200T-180
18 V
11.00 A
198 W
ATM 200T-190
19 V
10.50 A
200 W
ATM 200T-240
24 V
8.30 A
200 W
ATM 200T-480
48 V
4.17 A
200 W
INPUT
Voltage
AC 100 V 240 V
Frequency
50 Hz - 60 Hz
Current
2.4 A 1.0 A
Protection
Internal Primary Current Fuse
OUTPUT
Load Regulation
± 5 % (typical)
Ripple
1 % V p-p max. for output voltage at full load
Transient Response
0.5 ms for 50 % load change typical
Touch Current
< 100 µA
Protection
Short Circuit Protection ▪ Over Voltage Protection ▪ Over Current Protection
Over Temperature Protection
OTHERS
Cooling
Convection
Efficiency
Meet DoE Level VI
Holdup Time
10 ms at full load
Dielectric Withstand
AC 4000 V Primary Secondary
MTBF
300,000 calculated hours at 25 °C by Telcordia SR-332
ENVIRONMENT
Temperature
Operating: -20 °C 40 °C / Storage: -20 °C 80 °C
Humidity
Operating: 20 % RH 80 % RH / Storage: 10 % RH 90 % RH
CONNECTION
Output Connection
Cord: UL 2464 / UL 2095; 4 Pin Mini DIN Plug (48 V variant: 5.5 x 2.1 x 11 mm)
AC Inlet
P: IEC 60320 C14 Inlet (Protection Class I) 15 V variant not available
A: IEC 60320 C8 Inlet (Protection Class II)
Case Dimensions
204 mm × 81 mm × 42.5 mm
Weight
880 g (ref.)

Summary of content (2 pages)