Owner's Manual

ZEN-RIO-MAN-15V02 (1009) Copyright © 2015 De ne Instruments
2
Contents .......................................... 2
1 - Speci cations ............................. 2
2 - Unit Overview ........................... 3
2.1 - Casing & Terminals ............. 6
2.2 - LED Indicators ..................... 6
3 - Wiring & DIP Switches ............... 5
3.1 - Relays 1–16 ......................... 5
3.2 - Control Inputs 1–16 ............ 5
3.3 - Power .................................. 6
4 - Connecting To Your ZEN-16 ....... 7
4.1 - Expansion Terminals ........... 7
4.2 - So ware Setup ................... 7
CONTENTS
1
SPECIFICATIONS
16 isolated relay outputs Change over Form C (10A 250V AC or 10A 30V DC), 1kHz
scan rate. So ware selectable relay state.
16 selectable digital control inputs Input type select NPN (sink) or PNP (source)
from DIP switch A4 (see 2.5). 1kHz Input sample rate. Input voltage 5–24V.
LED indication on each relay output and control input channel (see 2.1–2.2)
Communication Via iC bus, 400kHz
DC power supply 24V DC ±15%
DIN rail mountable unit 35mm DIN rail
Dimensions (H x W x D) 59 x 255 x 144mm (2.32 x 10.04 x 5.67") - with plugs in