7.3 Error messages
Display red LED Buzzer Error relay Resetting
Error 1
Cover open
Error message is displayed
until the water tank carriage
(PH28) or the side cover
(PH28A) is inserted correctly
and locked.
ashes ––– activated Automatic resetting as
soon as the water tank
carriage (PH28) or the
side cover (PH28A) is
inserted correctly and
locked.
Cause: Water tank carriage (PH28) or side cover (PH28A) not inserted and locked.
Action/Remedy: Correctly insert water tank carriage (PH28) or side cover (PH28A) and lock it.
Error 2
Max Niveau
Error message is displayed
until reset.
ashes buzzes loudly
(can not be
switchedoff)
activated Switchunitoff,thenon
again.
Cause: Maximumwaterlevelinthebasetubexceeded.Safetyswitchhastriggered.
PH28: water tank not tight (tank cap not tight and/or level regulating valve in the tank cap
blockedordefective).
PH28A:inletvalvedefective.
Action/Remedy:PH28:Removethetankimmediately.Check/cleanllerneck,tankcapandlevelregulating
valveintankcap(replacetankcapifnecessary),thenclosetankcapcorrectly.
PH28A: check/replace inlet valve.
Error 3
Filltime
Error message is displayed
until reset.
ashes buzzes activated Switchunitoff,thenon
again.
Note: ThismessageisdisplayedonlyontheDefensorPH28A
Cause: Shut-offvalveinthewatersupplylineclosed.Internalwaterlter(neartotheinletvalve)
blocked.Inletvalvedefective.
Action/Remedy:openshut-offvalveinthewatersupplyline.Cleanwaterlter(seechapter6.3).Check/replace
inlet valve.
Error 4
No signal
Error message is alternating
with the standard operating
display.
ashes beepsbriey
every 6 min-
utes
activated Automatic resetting as
soon as the unit re-
ceivesasignalfromthe
radio humidity sensor.
Cause: TheDefensorPH28/PH28Adoesnotreceiveanysignalfromtheradiohumiditysensor(op-
tion).Batteryoftheradiohumiditysensorsoonemptyorradiohumiditysensordefective.
Radiohumiditysensorinstalledoutsidethesignalrangeof25m.
Note:Aslongastheunitdoesnotreceiveanysignalfromtheradiohumiditysensoritswitches
to the internal humidity sensor.
Action/Remedy:Replacethebatteryoftheradiohumiditysensor.Check/replaceradiohumiditysensor.Install
radio humidity sensor inside the signal range.