7.2 C 610 ECO
C 610-... ECO Unit 700 860 1000 1140
Introduction
Number of sections 2 x 6 2 x 7 2 x 8 2 x 9
Regulating the output Modulating
Output (80/60°C) PN
minimum kW 87 123 122 148
maximum kW 654 790 924 1062
Output (50/30°C) PN
minimum kW 94 131 130 156
maximum kW 706 854 998 1146
Nominal output (Hi)
minimum kW 91 128 127 153
maximum kW 672 808 942 1078
Combustion gas and by-products
Gas category (see table in "General Description" chapter)
Gas supply pressure mbar 17 - 25
Gas flow rate Gas H/E (15°C - 1013 mbar)
minimum m
3
/h 9.6 13.5 13.4 16.2
maximum m
3
/h 70 85.4 99.6 114
Gas flow rate Gas L/LL(15°C - 1013 mbar)
minimum m
3
/h 11.2 15.8 15.6 18.8
maximum m
3
/h 82.6 99.4 115.8 132.6
Average nitrogen oxide emission (NOx) mg/kWh < 60
Maximum pressure at the flue gas nozzle Pa 130
Combusted gas flow
minimum kg/h 153 215 214 257
maximum kg/h 1130 1360 1586 1814
Temperatures of the combusted gases at 80/
60°C
minimum °C 57
maximum °C 65
Boiler types: B23, C33, C53, C63, C83
Heating
Safety temperature °C 110
Water setting range °C 20 - 90
Water pressure minimum bar 0,8
Water pressure maximum bar 6
Water content l 120 142 164 186
Water resistance at
∆T = 10°C mmCE 4400 4800 4400 5000
Water resistance at
∆T = 20°C mmCE 1100 1200 1100 1250
Electricity characteristics
Power supply voltage V/Hz 230 / 50
Power consumption
minimum W 12
maximum W 694 980 1240 1684
Insulation class IP 21
Miscellaneous
Weight without water kg 820 920 1020 1120
Acoustic level at 1 meter dBA 63