Operating Instructions and Installation Instructions
AD Holdings ©2011
75
TransVu Express
Alarm Input
This menu allows conguration of the alarm settings, refer to ‘Installing the Unit’ for hardware
installation guidance.
Number This identies which input is being congured. The unit supports 32
alarm inputs.
Enabled Each input must be enabled to function. If the input is not enabled and
an alarm is received, the unit will not acknowledge the alarm.
Module The alarm contacts are connected via modules. Select the module that
the contact to be congured is in.
Contact Select the Contact within the module to congure.
N_O (Normally Open Contact) N_O indicates the non-alarm state of the input. Tick the N_O checkbox
to set the corresponding input to Normally Open. The alarm will then
trigger when the input is closed (shorted). If left as Normally Closed
(the default setting), the alarm will trigger when the input is opened.
Note: If EOL alarms are to be used, this option should not be selected i.e. leave set as
Normally Closed.
EOL The End Of Line (EOL) option enables the inputs to detect any
changes in the electronic input resistance. A change outside the
expected values will result in a Tamper Alarm (short circuit or open
circuit) being detected and the system switching to alarm mode.
Pulse Ext (s) A pulse extension is used to prevent double triggers on a single alarm.
The pulse extension time starts on an alarm trigger. If that contact is
triggered again after the rst alarm has nished but within the pulse
extension, the second trigger will not restart the alarm, but will extend
the current alarm duration. Enter the time in seconds for this extension.