Alarm Input
This menu allows conguration of the alarm settings, refer to ‘Installing the DV-IP HD Unit’ for
hardware installation guidance.
Number This identies which input is being congured. The unit supports
20 on-board alarms.
Enabled Each input must be enabled to function. If the input is not enabled
and an alarm is received, the unit will not acknowledge the alarm.
N_O (Normally Open Contact) By default an input will normally be closed, ticking the N_O box
forces the corresponding input open for alarm.
EOL The End Of Line (EOL) option enables the inputs to detect any
changes in the electronic input resistance. A change outside the
expected values will result in a Tamper Alarm (short circuit or open
circuit) being detected and the system switching to alarm mode.
Pulse Ext A pulse extension is used to prevent double triggers on a single
alarm. The pulse extension time starts on an alarm trigger. If that
contact is triggered again after the rst alarm has nished but
within the pulse extension, the second trigger will not restart the
alarm, but will extend the current alarm duration. Enter the time in
milliseconds for this extension.