Multiplying factor on motor speed (rpm) to give customer defined units.
Used to set-up a user security code. See section 6.6 Security codes on page 48.
0: keypad reference is zero
LASt:keypad reference is last value selected before the drive was powered down
PrS1:keypad reference is copied from preset speed 1
no: no action
rEAd:program the drive with the contents of the SmartStick
Prog:program the SmartStick with the current drive settings
boot: SmartStick becomes read only. The contents of the SmartStick will be copied to
the drive every time the drive is powered up.
Parameter copying is initiated by pressing the MODE key on exit from parameter
edit mode after Pr 28 has been set to rEAd, Prog or boot.
No Function Range Defaults Type
24
Customer defined scaling 0 to 9.999 1 RW
No Function Range Defaults Type
25
User security code 0 to 999 0 RW
No Function Range Defaults Type
26
Not used
No Function Range Defaults Type
27
Power up keypad reference 0, LASt, PrS1 0 RW
No Function Range Defaults Type
28
Parameter copying no, rEAd, Prog, boot 0:no RW
Before setting boot mode, the current drive settings must be stored in the SmartStick by
using Prog mode, otherwise the drive will trip on C.Acc at power-up.
NOTE
M
If parameter copying is enabled when no SmartStick is installed to the drive, the drive will
trip on C.Acc.
NOTE
The SmartStick can be used to copy parameters between drives of different ratings.
Certain drive dependant parameters will be stored on the SmartStick but will not be
copied to the cloned drive.
The drive will trip on C.rtg when being written to by a copied parameter set of a different
drive rating.
The drive dependant parameters are: Pr 06 Motor rated current, Pr 08 Motor rated
voltage, Pr 09 Motor power factor and Pr 37 Maximum switching frequency.
NOTE
Before the SmartStick /LogicStick is written to using Prog, the SmartStick/LogicStick will
need to be inserted into the drive at power up or a reset command performed when the
drive has been powered up, otherwise will trip on C.dAt when Prog command executed.
NOTE
For best motor performance, an autotune should be carried out after parameter copying
has taken place.
NOTE
When copying between drives of different ratings, bit parameters will not be copied.
NOTE