Instruction Manual
14
MIT-II - MIT/P - QUADROPAC DUP 500 14/04/2010 - 300015090-001-L
#SETTING x x x x x x The parameters are set using keys
or
.
Z
See also: Miscellaneous settings.
--
CONTRAST DISP. x x x x x x Adjusting the display contrast - -
BACK LIGHT xxx x xxON: The lighting is permanent if the circuit is in
Daytime period
. If the circuit displayed is in a
Night period, the backlighting is ECO.
ON ON, ECO
or OFF
ECO: If the circuit displayed is in Nighttime
period, the lighting is on for 2 minutes if a key on
the keyboard is pressed.
OFF: The display is never lit
SUM/WIN x x x x x x Summer/winter setting 22 °C 15 to
30 °C -
OFF
CALIBR. OUT x x x x x x Outside sensor calibration 0.0 -5.0 to
+5.0 K
CALIBR. ROOM A * x x x x x x Calibration of the room sensor on circuit A 0.0 -5.0 to
+5.0 K
OFFSET ROOM A * x x x x x x Room offset on circuit A 0.0 -5.0 to
+5.0 K
OFFSET ROOM B * x x x x x x Room offset on circuit B 0.0 -5.0 to
+5.0 K
ANTIFR. ROOM A * x x x x x x Room temperature antifreeze activation on circuit
A
6 °C 0.5 to
20 °C
CALIBR. ROOM B * x x x x x x Calibration of the room temperature sensor on
circuit B
0.0 -5.0 to
+5.0 K
ANTIFR. ROOM B * x x x x x x Room temperature at which the antifreeze mode
is activated on circuit B
6 °C 0.5 to
20 °C
#TIME . DAY x x x x x x The parameters are set using keys
or
.
Z
See also: Setting the time and the date
- Summer time.
--
HOURS xxx x xx
MINUTE xxx x xx
DAY xxx x xx
MONTH xxx x xx
DATE xxx x xx
YEAR xxx x xx
SUM. TIME: xxx x xxAUTO: automatic switch to summer time on the
last Sunday in March and back to winter time on
the last Sunday in October.
MANU: for countries where the time change is
done on other dates or is not in use.
AUTO AUTO or
MANU
Display
ROE-II ROE-H ROE+ ROE+TH SOLO,
NAPO
ROI+
Parameter set
Factory
setting
Adjustme
nt range
* The line or title is only displayed for the options, circuits or sensors actually connected.