Instruction Manual
12
MIT-II - MIT/P - QUADROPAC DUP 500 14/04/2010 - 300015090-001-L
6.1 Table of "User" setting
The different adjustable parameters are listed in their order of
appearance.
At the end of the intervention, the data is memorised after 2 minutes
or by pressing the AUTO key.
Display
ROE-II ROE-H ROE+ ROE+TH SOLO,
NAPO
ROI+
Parameter set
Factory
setting
Adjustme
nt range
#MEASURES Allows the values below to be read
TEMP.MIT x x x x x x Water temperature in the MIT-II module or
heating zone in the Quadro
--
HP FLOW TEMP. x x x Water temperature at the PAC outlet - -
SOURCE TEMP. x Refrigerant temperature at the heat pump source
end
--
COLD TEMP. x x Temperature of the PAC cold circuit - -
EVAPORATOR T. x Refrigerant temperature at the fin tube
exchanger outlet
--
OUTLET TEMP. B* x x x x x Water temperature in circuit B (Flow sensor) - -
WATER TEMP. * x x x x x Tank water temperature - -
ROOMTEMP. A* x x x x x Room temperature A - -
ROOMTEMP. B* x x x x x Room temperature B - -
OUTSIDE TEMP. x x x x x Outside temperature measured by the MIT-II
module
--
HP RETURN TEMP x x Return temperature - -
HP FLOW TEMP. x x Flow temperature - -
FLUID EVAP.T. x x Fin tube exchanger refrigerant temperature - -
FLUID COND.T. x x Refrigerant temperature at the heat exchanger - -
HOT GAS TEMP. x Refrigerant temperature at the compressor outlet - -
HP OUTSIDE T. x x x x Outside temperature measured by the PAC - -
HP FLOW TEMP. x Water temperature at the PAC outlet - -
HP RETURN TEMP x Return temperature - -
HP AIR IN T. x Outside temperature at the heat pump - -
EVAPORATOR T. x Refrigerant temperature at the fin tube
exchanger outlet
--
HOT GAS TEMP. x Compressor outlet temperature - -
PRESSION(BAR) x x x x x x Water pressure display - -
NB IMP.COMP. x x x x Number of PAC start-ups - -
NB IMP.COMP.1 x Number of start-ups on compressor 1 - -
RUNTIME COMP. x x x x x x Number of PAC operating hours
Number of hours' operation of compressor 1
--
NB IMP.COMP.2 x Number of start-ups on compressor 2 - -
RUNTIME.COMP.2 x Number of hours' operation of compressor 2 - -
CTRL x x x x x x Information reserved for the technician (Diematic
programme version)
--
* The line or title is only displayed for the options, circuits or sensors actually connected
.