User Manual
Code Faults Cause
of the
fault
Description Checking / solution
L00 PSU FAIL
PCU PSU PCB not connected Bad connection
PSU PCB faulty
4 Contact the professional who takes care of
maintenance of the appliance
L01 PSU PARAM FAIL
PCU The safety parameters are incorrect Bad connection
PSU PCB faulty
4 Contact the professional who takes care of
maintenance of the appliance
L02 DEF.OUTLET S.
PCU The boiler flow sensor has short-
circuited
Bad connection
Sensor fault
4 Contact the professional who takes care of
maintenance of the appliance
L03 DEF.OUTLET S.
PCU The boiler flow sensor is on an open
circuit
Bad connection
Sensor fault
4 Contact the professional who takes care of
maintenance of the appliance
L04 DEF.OUTLET S.
PCU Boiler temp too low Bad connection
Sensor fault
4 Contact the professional who takes care of
maintenance of the appliance
No water circulation
4 Vent the air in the heating system
4 Check the circulation (direction, pump,
valves)
4 Check the water pressure
L05 STB OUTLET
PCU Boiler temperature too high Bad connection
Sensor fault
4 Contact the professional who takes care of
maintenance of the appliance
No water circulation
4 Vent the air in the heating system
4 Check the circulation (direction, pump,
valves)
4 Check the water pressure
L06 BACK S.FAILURE
PCU The return temperature sensor has
short-circuited
Bad connection
Sensor fault
4 Contact the professional who takes care of
maintenance of the appliance
L07 BACK S.FAILURE
PCU The return temperature sensor is on
an open circuit
Bad connection
Sensor fault
4 Contact the professional who takes care of
maintenance of the appliance
L08 BACK S.FAILURE
PCU Return temperature too low Bad connection
Sensor fault
4 Contact the professional who takes care of
maintenance of the appliance
No water circulation
4 Vent the air in the heating system
4 Check the circulation (direction, pump,
valves)
4 Check the water pressure
MCA 15 - MCA 25 MCA 25/28 MI 6. Troubleshooting
23/08/2011 - 300024159-001-B