Operation Manual
3 Technical specifications
3.1 Homologations
3.1.1. Certifications
This product complies to the requirements to the european directives
and following standards:
4 2006/95/EC Low Voltage Directive. Reference Standards:
EN60335-1 / EN60335-2-40.
4 2004/108/EC Electromagnetic Compatibility Directive. Generic
standards: EN1000-6-3 , EN 61000-6-1.
Apart from the legal provisions and Directives, the additional
Directives described in these instructions must also be observed.
For all provisions and Directives referred to in these instructions, it is
agreed that all addenda or subsequent provisions will apply at the
time of installation
3.2 Technical specifications
3.2.1. Electricity supply
230 V AC (+/- 10%) - 50 Hz
400 V AC (+ 6%, - 10%) - 50 Hz (depending on the model)
3.2.2. Heat pump
Conditions of use:
4 Limit operating temperatures in Hot mode:
- Water: +18 °C / +60 °C (4, 6, 8, 11, 16 kW)
Water: +18 °C / +55 °C (22, 27 kW)
- Outside air:
-15 °C / +35 °C (4, 6 kW)
-20 °C / +35 °C (8, 11, 16, 22, 27 kW)
4 Limit operating temperatures in Cooling mode:
- Water: +7 °C / +25 °C (At less than 18°C, it is necessary to use
the HK24 insulation kit option)
- Outside air: +15 °C / +40 °C
4 Maximum operating pressure: 3 bar
AWHP-2 MIT-IN-2 iSystem
3. Technical specifications
10/06/2015 - 7616372-001-05
14