Chimney-Vent F lue Gas Temperature °C
(Net, M inus Roo m Temperature)
Carbon Dioxide [CO
2
] Content %
Chimney-Vent Flue Gas Temperature °F
(Net, Minus Roo m Temperature)
Chimney-Vent P ressure
Gas-Fired Appliance Vent Categorization
[According to ANSI Z21.13/CSA 4.9 Gas Boiler Standard]
Category I Appliance
(Negativev ent pressure)
A, B,L [C breeching o nly]
Positive
Negative
Category II Appliance
(Negativev ent pressure)
AL29-4C®o r 316SS
Category III Appliance
(Positivev ent pressure)
AL29-4C®o r 316SS
Category I V Appliance
(Positivev ent pressure)
AL29-4C®o r 316SS
Venting
Boiler breeching and main chimney
De Dietrich GT Series boilers are a high performance
boiler. The ue gas temperature can be less than 320°F
[160°C]. Special attention is required for the venting
of the boiler according to the specic site operating
conditions.
WARNING
The De Dietrich boiler can be operated at low ue
gas temperatures. As a result ue gas condensation
may occur and could accumulate in the breeching
and main chimney. Suitable provision for ue gas
condensation draining is required. A condensate TEE
tting shall be provided on the main chimney as close
as possible to the boiler breeching collar (See g
8553N143). Any horizontal portion of the breeching
shall be kept to minimum.
A vent category chart has been provided to further
assist the heating specialist to determine and evaluate
whether the correct venting is applied for each gas vent
category.