Chimney-Vent F lue Gas Temperature °C
(Net, M inus Roo m Temperature)
Carbon Dioxide [CO
2
] Content %
Chimney-Vent Flue Gas Temperature °F
(Net, Minus Roo m Temperature)
Chimney-Vent P ressure
Gas-Fired Appliance Vent Categorization
[According to ANSI Z21.13/CSA 4.9 Gas Boiler Standard]
Category I Appliance
(Negativev ent pressure)
A, B,L [C breeching o nly]
Positive
Negative
Category II Appliance
(Negativev ent pressure)
AL29-4C®o r 316SS
Category III Appliance
(Positivev ent pressure)
AL29-4C®o r 316SS
Category I V Appliance
(Positivev ent pressure)
AL29-4C®o r 316SS
Venting
Boiler breeching and main chimney
De Dietrich GT Series boilers are a high performance
boiler. The ue gas temperature can be less than 320°F
[160°C]. Special attention is required for the venting
of the boiler according to the specic site operating
conditions.
WARNING
The De Dietrich boiler can be operated at low ue
gas temperatures. As a result ue gas condensation
may occur and could accumulate in the breeching
and main chimney. Suitable provision for ue gas
condensation draining is required. A condensate TEE
tting shall be provided on the main chimney as close
as possible to the boiler breeching collar (See g
8553N143). Any horizontal portion of the breeching
shall be kept to minimum.
A vent category chart has been provided to further
assist the heating specialist to determine and evaluate
whether the correct venting is applied for each gas vent
category.