Operation Manual

62
GT 530A DDR_G30A/AE _IO_V4.0 09/2013
De Dietrich Cast Iron Boiler Temperature Controller Model S3NA (standard version)
1
Safety Hi-Limit (Manual Reset) Fixed Setting
120°C [248°F]
2
Panel fuse protection (resettable-breaker) 250v
10A rated
3 Main ON/OFF Switch
4 Operating limits dial conversion
5 Limit adjustable 40-100°C [104-212°F]
6
Aux Limit adjustable 40-100°C [104-212°F] op-
tionalusage, for 2 stage control (L-H-L) or ad-
ditional operating limit, additional relay required
not provided
7
Man/Auto/STB 3 position operating switch:Man
= Local paneloperationAuto = Remote control
operation–separate operating control required.
STB = Testing Safety limit function
8
Aux Switch –Optional usage (not part of safety
circuit) consult factory for appropriate use and
applications.
9
Provisional panel knockout for optional digital
control offering (consult factory for availability)
Connections
OVERVIEW OF COMPONENTS
1
2 3 4 5 6 7 8 9
S3NA
WARNING
All replacement and eld wiring min 18awg. Type
TEW or 1015 CSA/UL approved.
It is the sole responsibility of the installer/owner
that the controls are operating correctly
Wiring mistake can lead to personal injury
(including death) or property damage. Mark all
wires when prior to servicing or replacing wires or
components.
All water piping shall be arranged to avoid spray
or ingestion of water on control
Do not operate control if ingested or damaged by
water. Do not attempt to repair, lockout and tag
equipment replace control immediately.