Operation Manual
11
GT 530ADDR_G30A/AE _IO_V4.0 09/2013
Item Unit
Boiler Model Gt 530AE Series
-26 -27 -28 -29 -30 -31 -32
Firing Sequence Sonsult Burner Technical Data
Gas Input (CSA)
MBH 6,483 6,652 6,825 7,166 7,505 7,849 8,190
kW 1,900 1,950 2,000 2,100 2,200 2,300 2,400
# 2 Fuel Oil Input (CSA) US GPH 43.8 45.8 47.7 49.7 51.6 53.6 55.5
Output [Gas-Oil] (CSA)
MBH 5,524 5,668 5,815 6,105 6,394 6,687 6,978
kW 1,618.8 1,661.1 1,704.2 1,789.4 1,874.1 1,959.9 2,045.1
Cast Iron Sections # 26 27 28 29 30 31 32
Flue-way bafes # 10 10 10 10 10 10 10
Water capacity
US Gal 299.40 309.50 319.60 329.70 339.80 349.90 360.00
Liter 1,133 1,171 1,209 1,248 1,286 1,324 1,362
Water resistance
Delta T = °F
18°F Ft.H
2
O 3.48 3.67 3.86 4.26 4.67 5.1 5.56
27°F Ft.H
2
O 1.55 1.63 1.72 1.9 2.07 2.27 2.5
36°F Ft.H
2
O 0.87 0.92 0.97 1.06 1.17 1.28 1.39
Combustion
chamber
Dimensions
Diameter
(equivalent)
Inch
27.32
mm 694
Depth
Inch 113.97 118.34 122.71 127.08 131.45 135.82 140.19
mm 2,895 3,006 3,117 3,228 3,339 3,450 3,561
Volume
Ft
3
38.66 40.25 41.84 43.43 45.02 46.61 48.20
m
3
1.095 1.14 1.19 1.23 1.28 1.32 1.37
ASME MAWP (Water) PSIG 90 PSI-CRN Design registered for each Canadian Province
Min. Safety Relief Capacity MBH 6,076 6,234 6,396 6,716 7,034 7,356 7,676
S3NA
Electrical connection V/P/H 120/60/1 < 15 amp fused
Max. Water Temp.
Safety Limit [MR]
°F/ °C Fixed non adjustable 248°F [120°C]
Operating Water Tem-
perature Range
°F/ °C Adujstable 104-212°F [40-100°C] factory preset stop at 185°F [85°C]
Chamber resistance
Inch w.C 1.51 1.60 1.75 1.85 1.90 2.10 2.30
mbar 3.8 4.0 4.4 4.6 4.7 5.2 5.7
Gas-Vent Category # Cat I,II,III & IV- Direct vent (Sealed Combustion)
Boiler vent Connection Inch 20 20 20 20 20 20 20
Weight (Dry)
lb 12,111 12,501 13,891 13,281 13,671 14,061 14,451
kg 5,494 5,670 5,847 6,024 6,201 6,378 6,555