17.2 Boiler Control Settings
Site Applied Boiler Control Settings: [Setting Mode]
Advanced Setting Mode – Service Level
17.3 Routine Boiler Maintenance Checklist [Typical] – Does not respect all installations, guideline °only
Responsible
Description Schedule
Owner should at least be
familiar with what items
or areas need periodic
attention and
maintenance, the
licensed and authorized
service personnel shall
inform the owner what
symptoms to be aware
of and course of action
System pressure 11 – 100 psi
Monthly
Control functioning
Monthly
Seals or evidence of leaks
Monthly
Unobstructed combustion air supply, no
chemicals, garbage, gasoline, other combustible
materials or flammable liquids are stored near the
boiler.
Monthly
Check for water on the floor – around relief, vent
and other parts and piping of the water system
Monthly
Check operating limits for correct operation
Semi-annually
Ensure neutralization system is working Semi-annually
Check exhaust terminals for ice, snow or debris
buildup
Monthly
Check and test pressure relief safety valve
Annually
Check PH levels of condensate
Annually
Test temperature Hi limit functions
Annually
Checks for system leaks
Monthly
Check all auxiliary and other safety limits for
function and correct operation.
Annually
Check system water quality
Monthly
Check pump °operation
Monthly
Check fuel lines for leaks
Annually
Check combustion
Annually
Check control settings Annually
Clean combustion chamber Annually
Clean condensation collector and siphon Annually