Operation Manual

53
De Dietrich Gas 310/610 ECO
13.1.2 Pump run on time ()
Pump run on time can be adjusted (Please refer to
installation contractor)
-Press the
-key until the digit (with dot) appears in the
code-display.
-Press the
-key until the digit (with dot) appears in
the code-display.
-Set the required value, using the [+] and [-]-keys.
Press the
-key to stare the new value (value will flash twice).
Press the reset-key to return to operating mode.
Table 18 Adjustments pump run on time
13.1.3 Boiler control ()
Setting mode, parameter , can be set to different values
(see table 19).
Proceed as follows to change the boiler control:
Press the
key until the number (with dot)
appears in the code window.
Press the
key until the letter (with dot)
appears in the code window.
Use the [+] and/or [-] keys to specify the required
setting.
Press the
key to stare the new setting (flashes twice to confirm).
Press the reset key once to return to operating mode.
Table 19 Boiler control settings.
Example: boiler control
indicates that the boiler is controlled by means of a 0-10 volt signal modulated on the
basis of flow temperature (
= 4). Heat demand is on ( = 1).
13.2 Setting mode service level (only for the qualified service engineer) ()
To prevent accidental, unauthorized access by non-qualified persons the control system requires an input code to
gain access to the second level of boiler control.
-Press the
and keys simultaneously and hold. The code-display now shows a letter with a random
number in the
-display.
-While holding both keys pressed, set the
-display to , using the [+] or [-] keys and press the key.
-The display will flash twice, confirming acceptance of the access code.
-Release the keys and
 will disappear from the display.
Important!! Changing the pre-set values without reference to the tables contained in this manual may result
in incorrect boiler operation.
The service settings can now be reached by pressing the -key until the digit (with dot) appears in the
code-display. Set the required value, using the
key.
To deletes the service code, press the reset-key once.
If no keys are pressed over a 15 minute period, the service code will delete automatically.
Code

Description

Pump post purge = 10 seconds

Pump purge time for 1 to 15 minutes
( =  to )

Continuous pump operation
Code

Description


heat demand off

Heat demand on

on/off and High/Low

on/off and modulated on flow temperature

External 0-10v analog signal on temperature
External 0-10v analog signal on output %