Operation Manual

48
De Dietrich Gas 310/610 ECO
11.3 Display of value
The display has only two digits available therefore values over this are displayed as followed:
Values from 00 to 99 will be indicated without any decimals points.
Values from 100 to 199 will be indicated by a dot between both digits e.g.
 =100, =110, =199
Values from 200 to 299 will be indicated by a dot behind every digit e.g. = for 200, =210, =299
Value over 300 will be indicated by showing the thousands, hundreds, tens and units in separate
alternating pairs. (see section 12.2 and 12.5)
Negative values (for instance when using an external sensor or when sensors are not connected) will be
indicated by a dot behind the last digit, e.g.  indicates -10.
12.0 OPERATING MODE
12.1 Operating mode ()
During normal operation the code-display show the status (position in cycle) of the boiler, with the -display
indicating the actual flow temperature.
The digits or letters in the code-display have the following meaning:
Code
Description

Standby, there is no heat demand

Pre-ventilation (pre-purge time 30 seconds, post purge time 3 seconds)

Trial for ignition

Burner firing and flame detected

N/a

Waiting mode, startup check, air sensor LDs sufficient pressure

Control stop (burner off + post purge)
a) Flow temperature T1 > set pointF [+5°C]
b) Flow temperature T1 > desired set point modulating control 9°F [+5°C]
c) flow temperature T1 > parameter
d) Difference flow T1 and return T2 > 10°C (factory setting) Starting condition is ≤ 10°C

End of heating demand, pump post purge. During cycling prevention delay-time the boiler will
remain in state and will not react to heat demand.

N/a

Shut-off mode (see section 12.4)

Forced full load (HIGH)

Forced part load (LOW)

Gas leakage control

Burner cooling
Table 08