4 TECHINCAL DATA
4.1 Dimensions
fig. 03 Elevation drawings
Flow connection 3 inch ANSI 150# flange
Return connection 2.5 inch
Gas connection 2 inch NPT (BSP to NPT adapter provided)
Condensate drain 1 ¼ inch
Flue gas discharge 10 inch (starter piece may be required, consult vent manufacturer)
Combustion air supply 10 inch (starter piece may be required, consult vent manufacturer)
Dimensions
Gas 310 ECO Model
A B D N 0
mm
inch
mm
inch
mm
inch
mm
inch
mm
inch
310-5 1590 62 39/64 1312 51 21/32 1600 63 1463 57 39/64 1004 39 17/32
310-6 1590 62 39/64 1312 51 21/32 1600 63 1463 57 39/64 901 35 31/64
310-7 1980 45 61/64 1702 67 1990 78 11/32 1853 72 61/64 1110 43 45/64
310-8
1980
45 61 64
1702
67
1990
78 11/32
1853
72 61/64
1007
39 21/32
310-9 1980 45 61/64 1702 67 1990 78 11/32 1853 72 61/64 904 35 19/32
Unit
C
E
F
G
H
I
J
K
L
M
Inch
23 15/32
23 5/8
14 3/16
12 41/64
55 13/64
40 1/4
14 3/8
12 39/64
17 59/64
55 33/64
mm 596 600 360 321 1402 1022 365 320 455 1410
Unit
P
Q
R
S
T
U
V
Inch 26 25/32 7 7/8 50 51/64 28 23/64 57 3/8 6 45/64 21/64
mm 680 200 1290 720 1457 170 8
table 01, main dimensions, all fractions rounded up