Operation Manual

16
TRIO DT 250 - TRIO DT 350 16/07/2015 - 300028005-001-04
Adjustment parameter Fx - Maximum flow rate
Adjustment range: 0 ... 20 l/min
Factory setting: Installation 1: 6.7 - Installation 2: 4.2
In order for the regulator to calculate the quantity of heat produced by
the installation (parameter kWh), input parameter Fx. The parameter
Fx is equal to the flow in litres per minute in the solar circuit.
Determine the value Fx using the following tables, according to the
configuration of the installation and the number or surface area of the
collectors. When the flow is input incorrectly, the display kWh will also
be incorrect.
The quantity of heat (kWh value) can only be used for checks
carried out for personal reasons.
` Flat solar collectors
` Tubular solar collectors
Adjustment parameter MM - Operating mode
Adjustment range: 0 ... 4
Factory setting: 4
For inspection and maintenance work, it is possible to operate the
regulator in manual mode. To operate the regulator in manual mode,
it is necessary to input parameter MM from the following table.
Solar panel
installation
Area
m
2
Number of
panels
Flow rate
l/h
Flow rate
l/min
3 ... 5 1 or 2 400 6.7
6 ... 8 3 or 4 300 5
8 ... 10 4 or 5 250 4.1
8 ... 10 2x2 750 12.5
12 ... 15 2x3 670 11.2
16 ... 20 2x4 450 7.5
12 ... 15 3x2 850 14.2
18 ... 23 3x3 800 13.4
24 ... 30 3x4 650 10.9
16 ... 20 4x2 1200 20
24 ... 30 4x3 850 14.2
C000191
Number of panels
Flow rate
l/h
Flow rate
l/min
minimum: 1x4 820 13.7
1x5 750 12.5
1x6 680 11.4
1x7 610 10.2
1x8 540 9
1x9 470 7.8
1x10 250 4.1
2x3 1400 20
2x4 1250 20
2x5 1100 18.4
2x6 950 15.9
2x7 750 12.5
2x8 600 10
2x9 540 9
2x10 400 6.7
MM1 R1 R2
0Open Open
1Closed Open
2Open Closed
3Closed Closed
4 automatic automatic