Instruction Manual
n
Performances in hot mode with outside air temperature
at +2°C and outlet water temperature at +35°C (in
accordance with EN 14511–2)
AWHP 4 MR 6 MR -2 8 MR-2 11 MR-2 11 TR-2 16 MR-2 16 TR-2 22 TR 27 TR
Calorific output - A2/W35 kW 3.76 3.87 5.93 10.19 10.19 11.38 11.38 11.62 14.70
COP hot - A2/W35
3.32 3.26 3.20 3.20 3.20 3.27 3.27 3.01 3.10
Absorbed electrical power - A2/W35 kWe 1.13 1.19 1.85 3.19 3.19 3.48 3.48 3.86 4.74
Nominal amperage - A2/W35 A 6.1 6.1 8.2 10.7 6.2 14.6 8.4 9.7 11.8
n
Performances in cold mode with outside air
temperature at +35°C and outlet water temperature at
+18°C (in accordance with EN 14511–2)
AWHP
4 MR 6 MR -2 8 MR-2 11 MR-2 11 TR-2 16 MR-2 16 TR-2 22 TR 27 TR
Cooling output kW 3.84 4.69 7.90 11.16 11.16 14.46 14.46 17.65 22.2
EER
3.80 3.80 3.99 4.68 4.68 4.43 4.43 3.8 3.8
Absorbed electrical power kWe 0.72 1.15 2.0 2.35 2.35 3.65 3.65 4.65 5.84
n
General values
AWHP
4 MR 6 MR -2 8 MR-2 11 MR-2 11 TR-2 16 MR-2 16 TR-2 22 TR 27 TR
Sound pressure
(1)
dB(A) 41.7 41.7 43.2 43.4 43.4 47.4 47.4 51.8 53
Nominal water flow
(ΔT = 5K)
m
3
/h
1.04 1.04 1.47 1.88 1.88 2.67 2.67 3.8 4.6
Manometric height
available at nominal
flow rate
mbar 618 618 493 393 393 213 213 - -
Nominal air flow rate
m
3
/h
2100 2100 3000 6000 6000 6000 6000 8400 8400
Power voltage of the
outdoor unit
V 230 V~ 230 V~ 230 V~ 230 V~ 400 V3~ 230 V~ 400 V3~ 400 V3~ 400 V3~
Sound output
(2)
dB(A) 63.7 63.7 65.2 65.4 65.4 69.4 69.4 73.8 75
R410A refrigerant kg 2.1 2.1 3.2 4.6 4.6 4.6 4.6 7.1 7.7
refrigerant piping
connection (Liquid-
Gas)
inch 1/4-1/2 1/4-1/2 3/8-5/8 3/8-5/8 3/8-5/8 3/8-5/8 3/8-5/8 3/8-3/4 or
3/8-1
1/2-3/4 or
1/2-1
Max pre-loaded
length
m 10 10 10 10 10 10 10 30 30
Weight (empty) -
Outside unit
kg 42 42 75 118 118 130 130 135 141
(1) 5 m from the appliance, free field.
(2) Test conducted in accordance with the standard NF EN 12102
AWHP-2 MIT-IN-2 iSystem 6. Technical specifications
31/03/2014 - 7616372-001-02
30