Installation guide
Appendix A: Reporting Codes
Appendix A: Reporting Codes
The following tables contain Contact ID and Automatic SIA format reporting codes. For more information on reporting code formats and notes
about individual reporting codes, (see Section 5.6 Communicator Programming PWS Sect 6).
Contact ID
The first digit (in parentheses) will automatically be sent by the control. The second two digits are programmed to indicate specific information
about the signal. For example, if zone 1 is an entry/exit point, you could program the event code as [34]. The central station would receive the
following:
*BURG - ENTRY/EXIT - 1 where the “1” indicates which zone went into alarm.
SIA Format - Level 2 (Hardcoded)
The SIA communication format used in this product follows the level 2 specifications of the SIA Digital Communication Standard - October
1997. This format will send the Account Code along with its data transmission. The transmission will look similar to the following at the receiver:
N Ri01 BA 01
N = New Event
Ri01 = Partition /Area Identifier
BA = Burglary Alarm
01 = Zone 1
NOTE: A system event will use the Area Identifier Ri00.
Section # Reporting Code Code Sent When...
Dialer
Direction*
Automatic
Contact ID
Codes
SIA Auto
Rep Codes**
[320]-[323] Zone Alarms Zone goes into alarm A/R See Table 3 See Table 3
[324]-[327] Zone Restorals Alarm condition has been restored A/R See Table 3 See Table 3
[328] Duress Alarm Duress code entered at keypad A/R (1) 21 HA-00
[328] Opening After Alarm System disarmed with alarm in memory A/R (4) 58 OR-UU
[328] Recent Closing Alarm occurs within two minutes of system arming A/R (4) 59 CR-00
[328] Zone Expander Supervisory
Alarm/Rest.
Panel loses/restores supervisory transmission over the Keybus
from zone expansion modules, or keypads with zone inputs
A/R (1) 43 UA-00/UH-00
[328] Cross Zone (Police Code)
Alarm
Two zones on the same partition go into alarm during any given
armed-to-armed period (incl. 24Hr zones)
A/R (1) 39 BM-00/BV-00
[328] Burglary Not Verified With cross zoning enabled, a second zone alarm does not occur
before cross zone timer expires
A/R (3) 78 BG-00
[328] Alarm Cancelled A valid access code is entered during communications cancelled
window
A/R (4) A6 BC-00
[329] [F] Key Alarm/Rest. Keypad fire alarm (alarm and restore rep. codes sent together) A/R (1) 1A FA-00/FH-00
[329] [A] Key Alarm/Rest. Keypad auxiliary alarm (alarm and restore rep. codes sent
together)
A/R (1) AA MA-00/MH-00
[329] [P] Key Alarm/Rest. Keypad panic alarm (alarm and restore rep. codes sent together) A/R (1) 2A PA-00/PH-00
[329] Aux Input Alarm/Rest Option#23/24: a panic button wired to PGM 2 is pressed/access
code is entered
Option #04: a 2-wire smoke detector wired to PGM 2 goes into
alarm/alarm is cleared.
A/R
A/R
(1) 4A
(1) 11
UA-99/UH-99
FA-99/FH-99
[330]-[337] Zone Tamper/Restoral Zone is tampered / tamper condition restored T/R (3) 83 TA-ZZ/TR-ZZ
[338] General System Tamper/
Rest.
Enrolled module with tamper inputs has a tamper alarm/all mod-
ule tampers restored
T/R (1) 45 ES-00/EJ-00
[338] Keypad Lockout Maximum number of incorrect access codes has been entered at
a keypad
T/R (4) 61 JA-00
[339-341] Closings System armed (user 01-34, 40-42 indicated) O/C (4) A1 CL-UU
[341] Partial Closing One or more zones bypassed when system armed O/C (4) 56 CG-ZZ
[341] Special Closing Closing (arming) using one of the following methods: quick arm,
auto arm, keyswitch, function key, maintenance code, DLS soft-
ware, wireless key
O/C (4) AA CL-00
[341] Late to Close Whenever the Auto-arm prealert sounds (if the Late to Close
option is enabled)
O/C (4) 54 CI-00
[341] Exit Fault If exit fault pre-alert occurs and entry delay expires O/C (3) 74 EE-00
[342-344] Openings System disarmed (user 01-34, 40-42 indicated) O/C (4) A1 OP-UU
[344] Auto-arm Cancellation Auto-arm cancelled O/C (4) 55 CI-00
[344] Special Opening Opening (disarming) using one of the following methods: key-
switch, maintenance code, DLS software, wireless key
O/C (4) AA OP-00
[345]-[346] Battery Trouble/Rest. PC1616/PC1832/PC1864 battery is low/battery restored MA/R (3) A2 YT-00/YR-00
[345]-[346] AC Line Trouble/Rest. AC power to control panel is disconnected or interrupted/AC
power restored (Both codes follow AC Failure Comm. Delay.)
MA/R (3) A1 AT-00/AR-00
[345]-[346] Bell Circuit Trouble/Rest. Open or short circuit detected across bell terminals/bell circuit
restored
MA/R (3) 21 YA-99/YH-99