Installation guide

PowerSeries - PC1616/PC1832/PC1864
26
Section [702] Second International Option Code
Section [703] Delay Between Dialing Attempts
Program the time the panel will wait between dialing attempts to transmit a reporting event to the central station.
Valid entries are [001] to [255].
Section [800]-[851] Module Programming
The following program sections are used to program different modules that can be connected to the control panel. Refer to the respective
Installation Manual for installation and programming information
Section [801]: PC5400 Printer Module Programming
Section [802]: PC59xx VOX Module Programming
Section [803]: Alternate Communicator Programming
Section [804]: Wireless Programming
Section [805]: PC5100 Addressable Programming
Section [851]: T-Link Programming
Special Installer Functions
Section [899] Template Programming
Selecting [][8] [Installer Code] [899] displays the current 5 digit template programming code. Refer to Appendix C - Template Program-
ming for a detailed description of available templates and corresponding 5 digit codes. After entering a valid 5 digit template programming
code, you will be prompted to enter the following in the sequence below:
1. Central Station Telephone Number, enter 32 Character Telephone number
Program the required Central Station phone number. Press [#] to complete your entry. This phone number will be entered into programming
section [301].
2. Central Station Account Code, enter 6-digit code
Program the required Central Station Account Code. Press [#] to complete your entry. This account code will be entered into programming
section [310].
3. Partition Account Code, enter 4-digit code
This programming section will only be prompted if Contact ID has been selected as a communications format. Program the required Parti-
tion Account Code. Press [#] to complete your entry. This Partition account code will be entered into programming section [311].
4. DLS Access Code, enter 6-digit code
Program the required DLS Access Code. This Access Code will be entered into programming section [403].
5. Partition 1 Entry Delay 1, Partition 1 Exit Delay, enter each 3-digit delay time
Program the desired 3 digit Partition 1 Entry Delay (in seconds) followed by the desired 3 digit Partition 1 Exit Delay (in seconds). Press [#]
to complete your entry. These values will be entered in programming section [005] sub-section [01] entry 1 and 3 respectively.
6. Installers Code
Enter the required 4 or 6 digit access code installers access code (dependent on Section [701] option 5). Press [#] to complete your
entry.This Installer Access Code will be entered into programming section [006].
After the Installers Code has been programmed the keypad will return to base installers programming menu.
Option Description
[1] ON: the communicator uses 33/67 make/break ratio when pulse dialing. OFF: the system uses 40/60 make/break ratio.
[2] ON: the system dials regardless of the presence of dial tone after the first attempt. OFF: the system dials only if dial tone is detected.
[3] ON: changes the Test Transmission Cycle Time to minutes. OFF: sends a Test Transmission after the programmed number of days.
[4] ON: the system accepts 1600Hz handshake pulse formats. OFF: the system accepts 1400Hz or 2300Hz handshakes.
[5] ON: the system generates a tone for 500mS every 2 seconds indicating digital equipment is making the call vs. a voice call.
OFF: the system does not generate a tone.
[6] ON: the tone generated (2100Hz.) indicates that digital equipment is making the call. OFF: the tone is 1300Hz.
[7] ON: the DLS dowloading window is 1 hour. OFF: the DLS downloading window is 6 hours.
[8] ON: the system activates the bell output if a Failure to Communicate trouble occurs while the system is armed.
OFF: the system does NOT activate the bell output if a Failure to Communicate trouble occurs while the system is armed.