Installation guide
PowerSeries - PC1616/PC1832/PC1864
20
Section [301] to [303] Telephone Numbers
Program the phone numbers as required. Phone Number 3 is dedicated as a back-up to Phone Number 1. HEX digits can be included for
special applications:
HEX [A] Not used
HEX [B] Simulates a [] key press
HEX [C] Simulates a [#] key press
HEX [D] Additional dial tone search
HEX [E] 2-second pause
HEX [F] End of phone number marker
Section [304] Call Waiting Cancel String
Program the digits required to disable call waiting. If enabled, the system will dial the programmed string on the first dialing attempt.
Program unused digits with data [F].
Section [310] System Account Number
Program the System Account Number. Only the SIA format supports 6-digit account numbers. If a 4-digit account number is required,
program the last two digits as data [FF]. If using the SIA format, this account number will be used for all reporting events. If using a differ-
ent format, this account number will be used for all events that are not partition specific (for example, low battery, AC trouble etc.). For par-
tition specific events the system will use the programmed Partition Account Number. For all formats other than SIA, program a HEX [A] for
any digit [0] in the account number being used.
Section [311] to [318] Partition Account Numbers
Program the Partition Account Number for each active partition (Section [311] for partition 1, Section [312] for partition 2 etc.). When using
the Automatic SIA format, these account numbers are not used. The system will use the System Account Number for all reporting events.
For all formats other than SIA, program a HEX [A] for any digit [0] in the account number being used.
Section [320] to [349] Reporting Codes
Program the reporting code for all events to be transmitted. For description of when each reporting event will be transmitted, refer to
Appendix A – Reporting Codes. The panel also supports Automatic SIA and Automatic Contact ID reporting. Program data [00] to disable
the reporting of an event. If any other data is programmed (Data [01] to [FF]) the panel will automatically generate the correct reporting
event when transmitting to the central station. For all formats excluding Automatic SIA and Automatic Contact ID, the panel will not
attempt to report an event if data [00] or data [FF] is programmed for the reporting code.
Section [350] Communicator Format
Program the 2-digit number for the desired Communicator Format for the First Phone Number and Second Phone Number. When dialing the
Third Phone Number, the system will use the Communicator Format programmed for Phone Number 1. Valid entries are [01] to [13]. Refer
to the Programming Worksheet for a list of the available Communicator Formats. Refer to the PC1616/PC1832/PC1864 Reference Manual
for Communicator Format details.
Section [351] to [376] Communicator Call Direction Options
Reporting events are categorized into 5 groups; Alarm/Restore, Opening/Closing, Tamper Alarm/Restore, System Maintenance and Test
Transmissions. Program which Phone Number the control panel will use to transmit reporting events by turning the option ON in the correct
Section. Phone Number 1 and/or Phone Number 2 can be used.
Section [377] Communicator Variables
Program a 3-digit number for each program entry:
Swinger Shutdown (Alarms): Maximum number of alarm/restoral transmissions per zone. Valid entries: [001] to [014]. Program data [000] to
disable shutdown.
Swinger Shutdown (Tamper): Maximum number of tamper alarm/restoral transmissions per zone. Valid entries: [000] to [014]. Program data [000]
to disable shutdown.
Swinger Shutdown (Trouble): Maximum number of trouble alarm/restoral transmissions per trouble condition. Valid entries: [000] to [014].
Program data [000] to disable shutdown.
Communicator (Transmission) Delay: Time, in seconds, panel will delay reporting an alarm event. Valid entries: [000] to [255].
AC Failure Communication Delay: Time, in minutes, panel will delay reporting an AC trouble event. Valid entries: [000] to [255].