Installation guide
PowerSeries - PC1616/PC1832/PC1864
16
Section [019] Seventh System Option Code
Section [020] Keypad Zone Assignment
Enter the two-digit zone number to be assigned to each keypad assigned to a specific slot. Only one keypad can be assigned to a specific slot. See
Keypad Assignment. Valid entries are from [00] to [64].
Section [021] Eighth System Option Code
[6] ON: When an alarm is detected on a zone (with the Cross Zone attribute enabled), a timer is started. The alarm is not transmitted and
the bell output is not activated unless a second cross zone enabled zone is violated before the Cross Zone timer times out. OFF: the
system reports all alarms normally and logs and transmits a Police Code reporting code if a second zone alarm is detected during the
armed period.
[7] ON: the system restarts the Exit Delay (one time) if a Delay zone is violated and restored during the exit delay time. OFF: exit
delay does not restart.
[8] ON: the system activates the trouble beeps when an AC trouble is detected. OFF: the system does not annunciate AC troubles
using the keypad buzzer.
Option Description
[1] ON: the bell will sound for the duration of Bell Time Out if a wireless zone fault occurs while armed. OFF: Wireless zone faults
will not sound the bell
[2] ON: the trouble LED will remain illuminated if the trouble restores before being viewed in the trouble menu. OFF: the trouble
LED will be illuminated when a trouble occurs and deactivates when all troubles are restored.
[3] ON: When disarming, the keypad will display only the first alarm to occur during the last arming period. OFF: When disarming,
the keypad will display all zones that were in alarm during the last arming period.
[4] For Future Use
[5] ON: a module supervisory trouble causes the bell to activate. OFF: a module supervisory trouble will not activate the bell.
[6] ON: the green LED indicator on the keypads indicate the status of AC on the system. OFF: the green LED indicator on the
keypads indicate the partition ready status.
[7] ON: All user access codes can enter the User Functions menu. OFF: Only the Master Code can enter the User Functions menu.
[8] For Future Use
Option Description
[1] ON: Access codes are not accepted by the system during entry delay. OFF: An access code can be used to disarm the system
during entry delay
[2] Refer to the PC1616/PC1832/PC1864 Reference Manual for EN Entry Delay details.
[3] For Future Use
[4] For Future Use
[5] For Future Use
[6] ON: Key-switches and wireless can only disarm the system during an entry delay. OFF: Key-switches and wireless keys can
disarm the system regardless if entry delay is active or not.
[7] ON:
Installer Programming only accessible if the DLS window is open. OFF: Installer programming is accessible at any time
[8] ON: Arming will be inhibited until all troubles are restored. OFF: the system can be armed with a trouble present..