[014] Second System Option Code
Section [015] Third System Option Code Section
[6] ON: the Audible Exit Fault feature will be enabled. If a delay zone is not secured correctly and not force-armed, at the end of the exit delay,
the system will go into entry delay and turn ON the bell output. OFF: the keypad will sound the entry delay through the keypad as normal.
[7] ON: the system will NOT log additional alarms for a zone that has reached the swinger shutdown threshold.
OFF: all zone alarms will be logged.
[8] ON: Temporal Three Fire Signal is used to annunciate fire alarms (½ second ON, ½ second OFF, ½ second ON, ½ second OFF ½ second
ON, 1 ½ seconds OFF). OFF: the system will pulse the bell output (½ second ON, ½ second OFF).
Option Description
[1] ON: the system squawks the bell output once when a partition is armed, twice when disarmed. OFF: the bell output does not
activate.
[2] ON: the system squawks the bell output every 10 seconds during the auto-arm pre-alert. OFF: the bell output does not activate.
[3] ON: the system will squawk the bell output once every second during Exit Delay, 3 squawks per second for the last 10 seconds.
OFF: the bell output will not activate.
[4] ON: the system will squawk the bell output once every second during Entry Delay, 3 squawks per second for the last 10 seconds.
OFF: the bell output will not activate.
[5] ON: the system squawks the bell output once every 10 seconds when a trouble condition is present.
OFF: the bell output does not activate.
[6] ON: the system will beep the keypads once every second, and 3 times a second during the last 10 seconds, during exit delay when
the system is armed with a user code or armed in the Away mode. OFF: the keypads will not beep.
[7] ON: the exit delay will be terminated (reduced to 5 seconds) when a Delay 1 zone is violated and restored after the system is armed.
OFF: the exit delay will count down as normal.
[8] ON: the bell output will not timeout if a fire alarm occurs. The user must turn OFF the bell by entering a valid user code.
OFF: the bell output will timeout normally.
Option Description
[1] ON: the keypad [F] fire emergency key will be enabled. OFF: the keypad [F] fire emergency key will be disabled.
[2] ON: the keypad [P] panic emergency will be audible (bell output). OFF: the keypad [P] emergency key will be silent.
[3] ON: the Quick Exit feature will be enabled. OFF: the Quick Exit feature will be disabled.
[4]
ON: the Quick Arming [
][0] feature will be enabled. OFF: Quick Arming [][0] feature will be disabled.
If this feature is disabled, a valid user code must be entered after the Stay or Away function buttons are pressed.
[5]
ON: a valid user code must be entered after pressing [
][1] to access the Bypass feature. OFF: a user code is not required.
[6] ON: the Master Code (user code 40) can only be changed in Installer Programming. OFF: the Master Code can be changed using
the User Programming [
][5] command.
[7] ON: the system supervises the telephone line and displays a trouble if disconnected. OFF: the telephone line is not supervised.
[8] ON: the system activates the bell output if a telephone line trouble is detected while the system is armed. OFF: the system activates
the keypad buzzer trouble tone.