User`s manual
GFK-2334A Chapter 5 PROFIBUS Master Status and Diagnostics 5-23
5
Error Code 1
The bits that make up the Error Code 1 byte are defined below.
D7 D6 D5 D4 D3 D2 D1 D0
Error Class Error Code
Error Class Meaning Error Code Meaning
0 to 9 Reserved 0 to 15 Reserved
10 Application 0
1
2
3 to 7
8
9
10 to 15
Read error
Write error
Module failure
Reserved
Version conflict
Feature not supported
Device specific
11 Access 0
1
2
3
4
5
6
7
8
9
10 to 15
Invalid index
Write length error
Invalid slot
Type conflict
Invalid area
State conflict
Access denied
Invalid range
Invalid parameter
Invalid type
Device specific
12 Resource 0
1
2
3
4 to 7
8 to 15
Read constrain conflict
Write constrain conflict
Resource busy
Resource unavailable
Reserved
Device specific
13 to 15 Device Specific 0 to 15 Device specific
Error Code 2
Error Code 2 is Device specific. Please refer to the user documentation of that slave for
further details.