User`s manual

GFK-2334A Chapter 5 PROFIBUS Master Status and Diagnostics 5-15
5
Note: A GE Fanuc 90-30 PROFIBUS Slave (PBS201) returns 13 bytes (7 words) of
data. Word 10 needs to be 9 or larger.
(Word 11) Slave Number: Word 11 specifies the address of the slave to which
COMMREQ is directed. If the address of the master or a slave that is not on the bus is
entered, a Status response of 4 is returned.
Get Device Diagnostics Reply Data Format –
Response written to location specified by Words 8 & 9
Word Name Description
1
Command Code Echo of the Command Code = 4.
2 Size x of Diagnostics
Received
Size of the Extended Diagnostics received. This
will indicate the number of bytes.
3 Diag 0 (Low Byte)
Diag 1 (High Byte)
Extended diagnostic data bytes.
4 Diag 2 (Low Byte)
Diag 3 (High Byte)
Extended diagnostic data bytes.
2 + (x/2) Diag ….x (Low Byte)
Diag ….x+1 (High
Byte)
Extended diagnostic data bytes.