GFK-2334A Chapter 5 PROFIBUS Master Status and Diagnostics 5-13
5
Error Event Codes for Slave Devices (Error Remote Address Not Equal to 255)
Code Indication Source Corrective Action
0 No errors NA NA
2 Slave station reports data
overflow.
Master
Telegram
Check length of configured slave parameter or configuration
data.
3 Master is requesting a function
that is not supported in the slave.
Master
Telegram
Check if slave is PROFIBUS-DP norm compatible.
9 No answering data, although the
slave must respond with data.
Slave Check configuration data of the slave and compare it with
the physical I/O data length.
17 No response from the slave. Slave Check bus cable and bus address of slave.
18 Master not in the logical token
ring.
Master Check FDL-Address of master or highest station address of
other master systems. Examine bus cabling for bus short
circuits.
21 Faulty parameter in request. Master
Telegram
Master has a firmware issue.