Error Event Codes for PROFIBUS Master (Error Remote Address of 255)
Code Indication Source Corrective Action
0 No errors are present. None None.
50 USR_INTF-Task not found. Master Firmware is invalid. Module must be
updated.
51 No global data-field. Master Firmware is invalid. Module must be
updated.
52 FDL-Task not found. Master Firmware is invalid. Module must be
updated.
53 PLC-Task not found. Master Firmware is invalid. Module must be
updated.
54 Non-existing master parameters. Master Download hardware configuration.
55 Faulty parameter value in the master
parameters
Configuration Firmware is invalid. Module must be
updated.
56 Non-existing slave parameters. Configuration Download hardware configuration.
57 Faulty parameter value in a slave parameters
data file.
Configuration Check GSD file for possible incorrect slave
parameterization values.
58 Duplicate slave address. Configuration Check configured slave addresses in
project.
59 Configured send process data offset address of
a slave is outside the allowable range of 0—
255.
Configuration Check slave configuration in project.
60 Configured receive process data offset address
of a slave is outside the allowable range of 0—
255.
Configuration Check slave configuration in project.
61 Data areas of slaves overlapping in the send
process data.
Configuration Check slave configuration in project.
62 Data areas of slaves are overlapping in the
receive process data.
Configuration Check slave configuration in project.
63 Unknown process data handshake. Master Problem with master’s startup parameters.
64 Free RAM exceeded. Master Master has a hardware issue.
65 Faulty slave parameter dataset. Configuration Check GSD file for possible incorrect slave
parameterization datasets.
202 No memory segment free. Master Master has a hardware issue.
212 Faulty reading of a database. Configuration Execute download of configuration
database again.
213 Structure used by the operating system is faulty. Master Master has a hardware issue.
220 Software Watchdog error. Host Firmware watchdog has an error.
221 No Data Acknowledge in process data
handshake.
Host Firmware is having trouble with Host
acknowledgement.
222 Master in Auto Clear mode Slave Device The auto clear mode was activated,
because one slave is missing during
runtime.
225 No further segments. Master Master has a hardware issue.