User`s manual

GFK-2334A Chapter 3 PROFIBUS Master CPU Configuration 3-9
3
Parameters Tab of the Master Properties Dialog Box
Scan Cycle Times
Typical
This field displays the estimated time (µs) required for one scan of the PROFIBUS network. This is a
read-only field.
Minimum
The minimum I/O scan time in 100 microsecond increments. This may be required if the I/O
modules are restricted in how often they can be scanned. To use this parameter, click the Minimum
check-box to activate it. Then enter the value in the field next to it. The value you enter here
represents the number of 100 microsecond increments. For example, in the figure above, the value
is 2 x 100 = 200 microseconds.
Range is 2 to 65535.
Scan Cycle
Times
Parameter
Group
These parameters allow you to set minimum and maximum scan cycle times for the Watchdog
timer.
Auto
The maximum I/O scan time and Watchdog timer are assigned automatically based on the number
of slave devices configured.
Maximum
The maximum I/O scan time in 10 millisecond increments. If the scan time exceeds this value, the
PROFIBUS master faults all the slaves, reinitializes them, and brings them back online. When the
maximum I/O scan time is updated, the Watchdog timer is also updated.
Range is 12 to 65535.
Watchdog
If a PROFIBUS slave does not receive any communication from its master within the Watchdog
time, the slave generates a fault, the outputs are set to 0, and the slave is reinitialized by the
PROFIBUS master card. Assigning a value affects the maximum cycle time.
Options Parameter Group
Repeater
Select this check box if there are repeaters on the network.
FMS Devices
Select this check box if there are PROFIBUS FMS (FieldBus Message Specification) devices on the
network.
Stay Offline on
Error
Select this check box if you want the PROFIBUS master to stay offline when the Token Error Limit
or response Error Limit is exceeded within 256 token cycles.